IMPEDANCE-BASED ANALYSIS OF CONTROL INTERACTIONS BETWEEN
CONVERTER-INTERFACED GENERATION AND THE GRID
The increasing integration of Converter-Interfaced Generation (CIG) into modern
power systems introduces new stability challenges associated with the interaction between
converter controls and the electrical grid. Wind power plants connected to weak grids are
particularly susceptible to oscillatory instabilities arising from these interactions. This
work investigates an impedance-based approach for characterizing such control interactions
and assessing their impact on system stability. A systematic methodology combining
short-circuit ratio (SCR) assessment, frequency scanning, Bode and Nyquist analyses, and
time-domain validation is applied to three cases with transmission line lengths ranging
from 250 km to 450 km, resulting in SCR values from 2.10 to 1.23. The results show that
weaker grid conditions lead to increasingly pronounced oscillations in the active power
and Phase-A current, while the dominant oscillation frequency decreases from 111 Hz to
101 Hz and 90 Hz, progressively approaching the 60-Hz fundamental frequency. Timedomain
simulations and Fourier analysis validate the frequency-domain results, identifying
spectral components at approximately 111 Hz, 98 Hz, and 90 Hz, respectively. The
results demonstrate the effectiveness of the proposed impedance-based methodology for
identifying oscillatory instabilities and characterizing control interactions in wind power
plants connected to weak grids.